Flame Detector X3301

Detection of Fires in their early stages using multispectral infrared technology with highest possible suppression of false alarms

Technical Specification

Summary

Detection of flames in an early stage with multispectral infrared technology with highest possible suppression of false alarms


Specifications

Spectral sensitivity: multispectral IR range
Viewing angle: 90°
Reaction time: 10 seconds
Inclination angle when installed: min. 10°
Ambient temperature range: non-ex zones: -40 °C to +75 °C [-40 °F to 167 °F], ex-zones: -55 °C to +125 °C [-67 °F to 257 °F]
Storage temperature range: -55 °C to +85 °C [-67 °F to 185 °F]
Relative atmospheric humidity: 0 to 95 %, non-condensing
Application: in zones with daylight, artificial light and interference sources, fire detection and alarm system (FC 7000 series), spark extinguishing system (CC 7000, CC 5000 series), ex-free zones and ex-zones (0539 II 2 D Ex tb IIIC T130 °C / 0539 II 2 G Ex d IIC T6 – T5 Gb)
Supply voltage: +24 VDC (min. 18 VDC, max. 30 VDC)
Ripple: max. 2 V (peak - peak)
Power requirement: without heating: 4 W in fault-free state, 5.2 W in alarm state, heating only max. 8 W
Starting time of detector: 30 seconds
Output relays: fire alarm relay, form C, 5 A at 30 VDC, fault relay, form A, 5 A at 30 VDC, auxiliary relay, form C, 5 A at 30 VDC
Housing material: copper-free aluminum, painted red
Conductor cross-section of connecting terminals: max. 2.5 mm²
Protection type: IP 66
Dimensions: approx. 254 x 119 x 122 mm [10 x 4.6 x 4.8 in]