LS Extinguishing Device

Extinguish sparks with our LS Soulutions

Technical Specification

In a brief

Automatic extinguishing devices consist of the components extinguishing nozzle, valve, flow test, ball valve and terminal box. Wear-free stainless steel nozzles create a fine water mist for reliable extinguishing of the danger potential. An internal shutter cone protects the extinguishing nozzle from malfunctions by material penetration. Different extinguishing nozzles allow the use in many different appilcations.


Specifications

Operating pressure: 58 to 145 psi [4 to 10 bar]
Ambient temperature: 41 °F to 140 °F [+5 °C to +60 °C]
Temperature in material flow: 41 °F to 176 °F [+5 °C to +80 °C]
Storage temperature: 23 °F to 140 °F [-5 °C to +60 °C ]
Extinguishing medium: water
Smallest clear width of the extinguishing device: 0.3 mm, If the water is very hard, an additive approved by GreCon can be used to reduce deposits on fittings and pipes. Please contact our customer service.
Weight: LS1: 9.74 lbs [4.42 kg], LS2: 12.78 lbs [5.80 kg]
Model: 1" / DN 25, All connecting elements are to be executed according to EN10242, if applicable.
Use with control consoles: CC 5000, CC 7000 series