Technical Specification
Summary
Detection of flames in an early stage with multispectral infrared and ultraviolet technology in a large application range with highest possible suppression of false alarms.
Specifications
Spectral sensitivity: | UV and far IR range |
---|---|
Viewing angle: | 90° |
Ambient temperature range: | -40° C to +75° C [-40 °F to 167 °F] |
Application: | in areas with daylight and/or artificial light |
Ex-classification: | Ex II 2 GD T5T6 T86°C |
VdS: | class 1, 23 m visibility, G203085 according to EN 54-10 |
Mains voltage: | +24 V ± 10 % |
Current drawn: | 200 mA ± 10 % |
Output signal: | 3 potential-free contacts: alarm, pre-alarm, trouble |
Test signal: | self-monitoring optic |
Status indication: | tricolor LED on device |
Connection terminals: | 12 AWG (2.5 mm²) to 22 AWG (0.3 mm²) |
Housing material: | copper-free aluminium, lacquered |
System of protection: | IP 66 |
Dimensions: | approx. 250 x 120 x 120 mm [9.8 x 4.7 x 4.7 in] |
Thread: | lead-through connection 3/4 inch NPT or M25 |
Weight: | approx. 2.7 kg |